HZ2181X 10A 3 Phase transformer DC resistance test instrument is a new instrument which designed for quick test of high-capacity transformer DC resistance with magnetic assist method.The method can test DC resistance of core five-limb and delta connected in the low voltage side of transformer quickly and accurately. It can be completed one time for normal YNd connected transformer,and there are different test methods for different type windings which improves greatly test speed.The instrument completes the whole process by MCU,which has perfect functions of protecing back-EMF and anti-interference on the scene, also has functions of storeing data with U-Disk, printing and communicateing with computer,protecting to avoid wrong connection AC380V. The instrument is a successor in level of 220kv-500kv transformer dc resistance test.


I.Main Technique Indexes and Using Conditions

1.1 Main technique indexes

Constant electric current: 1A  10A

Testing range: 1A: 100mΩ20Ω

            10A: 1mΩ2Ω

1A Three channels: Less than or equal to 10Ω

10 A Three channels: Less than or equal to 1Ω  

Accuracy:±0.2 percent

Resolution ratio: 0.1μΩ

External dimension:418mm290mm300mm

Weight: 15kg

1.2 Using conditions

Environment temperature : 0ºC40ºC

Environment humidity: Less than or equal to 80 percent RH

Power supply:AC198V242V

Power frequency: (50±1)HZ