HZ-501A Pencari Kerosakan Kabel Kuasa Elektrik Bawah Tanah
Harga Pencari Kerosakan Kabel Kuasa Bawah Tanah HZ-501A

Terutamanya untuk wujud bersama dengan rintangan rendah atau rintangan kerosakan tinggi
Kesalahan rintangan rendah: jika kerosakan penebat kabel, boleh terus menggunakan kaedah ujian nadi voltan rendah satu fasa kelas atau fasa kepada kerosakan bumi, dipanggil kebocoran kesalahan rintangan rendah, kesalahan rintangan rendah. Nilai rintangan am adalah kurang daripada seratus ohm. Jika nilai rintangan adalah sifar, ia dipanggil kerosakan litar pintas, yang merupakan kes khas kerosakan rintangan rendah
Leakage of high impedance fault: if the cable insulating medium has been damaged and fixed channel resistance, but the fault cannot be directly used cable fault tester by "low pressure pulse measurement method" called leakage of high fault resistance, the resistance is usually in the hundreds of ohms or more. When the DC leakage voltage test is done on the spot, the leakage current value increases continuously with the increase of the DC voltage, and exceeds the standard value of the cable itself. Leakage of high resistance and low resistance fault are relatively described and there is no distinctive difference between them.
Flashover kesalahan rintangan tinggi: Flashover kesalahan rintangan tinggi dalam julat voltan pra ujian kabel, apabila voltan pra ujian kabel digunakan pada nilai tertentu, nilai arus kebocoran kabel tiba-tiba meningkat, yang sangat melebihi nilai subjek. nilai standard kabel yang diperlukan, jenis kegagalan ini dipanggil flashover kesalahan rintangan tinggi. Walaupun penebat kabel rosak, ia tidak membentuk saluran rintangan tetap.
Kaedah diskriminasi ciri-ciri kerosakan kabel kuasa
Tiga ciri kerosakan kabel kuasa:
(1) Judged by MΩmeter, multi meter.
(2) Diadili oleh keputusan pra{1}}kabel
(3) Diadili oleh pra-pencari kabel kuasa HZ-501A
Dalam keadaan biasa, rintangan rendah, kerosakan litar terbuka boleh dinilai secara langsung oleh meter Ohm atau HZ-501A Power cable flashover instrumen gelombang ujian impuls.
Program ujian kerosakan kabel kuasa.
Dengan menggunakan instrumen flashover HZ-501A untuk mengesan kerosakan kabel, prosedur berikut biasanya diperlukan:
(1) Analisis ciri kerosakan kabel dan pelajari tentang voltan berkadar kabel dan bahan penebat.
(2) Using the HZ-501A Power cable Flashover instrument's impulse method to detect the cable length, and also to calibrate the radio wave speed in the fault cable.
(3) Dengan memilih kaedah ujian yang sesuai, gunakan instrumen lampu kilat HZ-501A Power untuk pra-mencari kerosakan kabel.
(4) Untuk menyematkan kesalahan kabel kuasa dengan tepat, masukkan laluan kabel bawah tanah, kedalaman dan pengesanan titik kerosakan.
(5) Menggunakan kaedah analisis toleransi pada keputusan ujian kerosakan kabel (mengukur toleransi, memindahkan toleransi kelajuan, toleransi penghakiman, toleransi instrumen).

Indeks Spesifikasi Utama Sistem
1) Platform operasi cip tunggal, kaedah pengendalian skrin sentuh-:
2)System functions: Fault distance measurement,Fault locating,transmission speed test,fault resistance,Power cable route tracing,buried depth detection etc
3)Detecting method: Low voltage impulse,Flash over method,Audio frequency method,Acoustic magnetic synchronous method,Valley value method,Peak method,Electromagnetic induction etc.
4)Display control: Flashover instrument: 8inchesindustrialgrade LCD, Battery inside, can workfor6 hours continually; others are Pointer table display
5)Detection range: testing distance: 30km, detection depth: 2-5m
6)Measurement accuracy: Pre-testing tolerances: ±10m (absolute value) or 1 percent (relative value), Precisely detecting tolerances: ±0.2m (Locating,route,depth)
7)sampling frequencies: 80MHz,40MHz,20MHz,10MHz
8)sampling method: automatic continuous sampling, no any discharging wave form can be left out absolutely.
9)low voltage impulse: 0.05/0.1/0.2/0.5/1/2/8uS, seven
10)Output power: Route power: 100W,Impact power: 0-400W
11)Impact high voltage: 0-35kV
12)short circuit current: 0-320mA
13)Burn through power: 0-1225J
Catatan
A During testing if it occurs abnormal, press the "stop" button or turn off the power switch to ensure safety.
B Tidak kira apa ujian, kabel yang diuji mesti dilepaskan sepenuhnya sebelum menanggalkan kabel voltan tinggi.
Masalah biasa dan Penyelesaian
1. Tiada jawapan selepas mula:
l Periksa bekalan kuasa AC 220V;
l Periksa sama ada fius adalah baik
2. But voltan tidak normal
l Periksa wayar tanah, wayar tanah voltan tinggi adalah baik dan sama ada tombol voltan pelarasan longgar;
3. High voltage can't be started.
l Check if "Adjust Voltage" knob at zero;
4. Butang berhenti tiada tindak balas
l Tekan butang berhenti selama 2 hingga 7 saat, atau apabila menekan butang berhenti, untuk menarik tuil permulaan.



Cool tags: HZ-501A Pencari Kerosakan Kabel Kuasa Elektrik Bawah Tanah, China, pembekal, pengilang, harga, untuk dijual, peralatan pengesan kerosakan kabel bawah tanah, mesin pengesan kerosakan kabel, pengesan kerosakan kabel elektrik, sistem lokasi kerosakan kabel, pengesan kerosakan kabel tdr semua dalam satu, kerosakan kabel terletak, sistem pengesan kerosakan ujian kuasa 32kv, pengesan kerosakan kabel tembaga, Peralatan pengesan kerosakan kabel, penguji kabel tdr, hz-501a, Pencari Kerosakan Kabel Kuasa LV, kilang pengesan kerosakan kabel, pengesan kerosakan kabel bawah tanah